TOXFREE ZH RZ1 (AS) AL

Aluminium halogen free (LSZH) cable for power transmission


TOXFREE ZH RZ1 AS AL is an aluminium LSZH cable for fixed installations. These cables are especially recommended for installation in public places and in instalations where safety is a priority.

TOXFREE ZH RZ1 AS AL cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE

RoHS

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

LSZH (Low Smoke Zero Halogen) based on  UNE-EN 60754-1 and IEC 60754-1.

Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%

Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

Mechanical performance

Minimum bending radius: x 5 cable diameter.

Impact resistance: AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant: UNE 211605.

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Distribution network.

TOXFREE ZH RZ1 AS AL cable design

Conductor

Aluminium, class 2, based on UNE-EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE).

Outer sheath

Low Smoke Zero Halogen (LSZH) polyolefin. Green colour, non-toxic and fire retardant.


  • LOW VOLTAGE 0,6/1kV

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Maximum service temperature: 90ºC.

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

  • Industrial use / Distribution network.

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

  • UV Resistant: UNE 211605.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%

  • LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x 15 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPLICATIONS

  • Distribution network.

  • Industrial use.

APPROVALS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 / UNE 21123-4

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

Technology


  • 1. Conductor
    • Aliuminium, class 2, based on UNE-EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE).
  • 3. Outer sheath
    • Low Smoke Zero Halogen (LSZH) polyolefin. Green colour, non-toxic and fire retardant.

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.



Your message has been sent. Thank you

To download the cable datasheet, please complete the form below


Your message has been sent. Thank you