TOXFREE ZH RZ1MZ1-K (AS)

Halogen free (LSZH) armoured cable with galvanized steel wire armour.


TOXFREE ZH RZ1MZ1-K AS is a LSZH is a safety cable. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment. For this reason, its use is highly recommended for public places, in hazardous areas with explosive gas atmospheres (ATEX), and installations in general where the cable is subject to risk of mechanical aggresion.

TOXFREE ZH RZ1MZ1-K AS cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE

RoHS

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

LSZH (Low Smoke Zero Halogen) based on  UNE-EN 60754-1 and IEC 60754-1.

Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%

Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

Mechanical performance

Minimum bending radius: x10 cable diameter.

Impact resistance: AG4 High severity.

Rodent proof

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant: UNE 211605.

Potentially explosion hazard locations. (ATEX)

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Potentially explosion hazard locations. (ATEX)

TOXFREE ZH RZ1MZ1-K AS cable design

Conductor

Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE).

The standard identification of insulated conductors is the following:

1 x   natural

2 x  Blue + Brown

3 G  Blue + Brown + Green/yellow

3 x  Brown+ Black+ Grey

4 G  Brown + Black + Grey + Green/yellow

4 x  Brown + Black + Grey + Blue

5 G Brown + Black + Grey + Blue + Green/yellow

Armour bedding

Low smoke zero halogen (LSZH) polyolefin inner sheath.

Armour

Galvanized steel wire armour.  Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable.

Outer sheath

Low Smoke Zero Halogen (LSZH) polyolefin. Green colour, non-toxic and fire retardant.


  • LOW VOLTAGE 0,6/1kV

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 603...

  • Maximum service temperature: 90ºC.

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN...

  • Industral use / Potentially explosion hazard locations. (...

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

  • Potentially explosion hazard locations. (ATEX)

  • UV Resistant: UNE 211605.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%

  • LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.

MECHANICAL PERFORMANCE

  • Impact resistance: AG4 High severity.

  • Minimum bending radius: x10 cable diameter.

  • Rodent proof

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPLICATIONS

  • Industrial use.

  • Potentially explosion hazard locations. (ATEX)

APPROVALS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 / UNE 21123-4

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE).
    • The standard identification of insulated conductors is the following:
    • 1 x natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 3 x Brown+ Black+ Grey
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
  • 3. Armour bedding
    • Low smoke zero halogen (LSZH) polyolefin inner sheath.
  • 4. Armour
    • Galvanized steel wire armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable.
  • 5. Outer sheath
    • Low Smoke Zero Halogen (LSZH) polyolefin. Green colour, non-toxic and fire retardant.