TOPFLEX V-K H05V-K & H07V-K

Electric cabinet wiring and domestic use.


TOPFLEX® H05V-K & H07V-K cable has been specially designed for installations that require a flexible cable due to the complex nature of their layout. This cable is specially suitable for domestic wiring. It may also be used for equipment wiring, distributors, cabinets and lighting. It is also recommended for installation under false ceilings. Cables with cross section up to 1 mm2 are especially suited for signalling and monitoring installations.

DOWNLOAD DoP

  • LOW VOLTAGE 300/500 V · 450/750 V

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 603...

  • Maximum service temperature: 70ºC.

  • UNE-EN 60332-1

  • Domestic use / Electrical panel wiring

  • Eca

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 300/500 V · 450/750 V

  • Rated Voltage: H05V-K (up to 1 mm2): 300/500 V.
    H07V-K (from 1,5 mm2 onwards): 450/750 V.

FIRE PERFORMANCE

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

THERMAL PERFORMANCE

  • Maximum service temperature: 70ºC.

  • Maximum short-circuit
    temperature: 160ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

MECHANICAL PERFORMANCE

  • Minimum bending radius: x5 cable diameter.

WATER PERFORMANCE

  • Water resistance: AD3 Sprays

Other properties


APPROVALS

  • AENOR

  • CE

  • HAR

  • RoHS

  • SASO

  • SEC

APPLICATIONS

  • Domestic use.

  • Electrical panel wiring.

BASED ON

  • EN 50525-2-31 / IEC 60227-3

PACKAGING

  • Blue 2,5 mm2 100 m

  • BOX COLOUR GUIDE

  • Brown 4 mm2 100 m

  • COLOUR CROSS SECTION LENGHT (M) PER BOX

  • Green 1 mm2 100 m or 200 m

  • Grey 6 mm2 100 m

  • Red 1,5 mm2 100 m or 200 m

  • Small cross sections (from 0,75 mm2 to 6 mm2) are supplied in high resistant colour boxes (see table below). Medium cross sections (from 10 mm2 to 35 mm2) are supplied in 100 m sealed coils. Cross sections > 35 mm2 are supplied in drums.

  • Violet 0,75 mm2 100 m

CONSTRUCTION PRODUCT REGULATION

  • Eca

International norm

  • IEC 60332-1

INSTALLATION CONDITIONS

  • In conduit.

OTHERS

  • Meter by meter marking (from 10 mm2 onwards).

National norm / European:

  • UNE-EN 60332-1

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Extra sliding PVC.
    • The standard identification of insulated conductors is the following:
    • Blue RAL 5015
    • Brown RAL 8003
    • Black RAL 9005
    • Red RAL 3000
    • Yellow/green RAL 1021 / RAL 6018
    • Grey RAL 7000
    • Dark Blue RAL 5003
    • White RAL 9010
    • Orange RAL 2003
    • Violet RAL 4005
    • Other colours available on request

Other cables with similar properties