Topcable Low voltage cables Medium voltage cables Topmatic

LME Cotizaciones

Top Cable

X-VOLT RHZ1 (S) Cu / OL / 2OL
MEDIUM VOLTAGE
6/10 kV - 18/30 kV
IEC 60502-2
Reference Norm


X-VOLT  RHZ1 (S) Cu / OL / 2OL

Conductor:
Annealed electrolytic copper conductor, class 2.
Optionally, with longitudinal sealing (cable type -2OL).

Internal semiconductor:
Screen above the conductor, made of thermosetting semiconductor material.

Insulation:
Cross-linked polyethylene (XLPE), cross-linked in dry nitrogen atmosphere.

External semiconductor:
Screen above the insulation, made of thermosetting and strippable semiconductor material.

Copper screen:
Screen of Cu wires and cross-wound of Cu tape, with a minimum cross-section of 16 mm2

Longitudinal sealing:
Hygroscopic tape completely (cable type –OL and -2OL).

External sheath:
External sheath of fire-retardant and halogen-free polyolefin, red colour with two grey bands. (for S type)

Applications:
Cable for fixed installations. Suitable for the transmission and distribution of electricity in a medium voltage network. Can be used indoors, outdoors and in underground applications.
Halogen-free cable with low emission of smoke and non-propagator of flame. Safety cable (S).

CHARACTERISTICS

Design standards:

IEC 60502-2

Nominal voltages:
6/10 kV, 8.7/15 kV, 12/20 kV and 18/30 kV

Maximum temperature of the conductor:
90ºC

Maximum temperature in short circuit:

250ºC (maximum 5 s)

Bending radius:
15 x Ø ext.

Halogen-free:

as per UNE-EN 50267

Low emission of smoke:
as per UNE-EN 61034

Non-propagator of flame:

as per UNE-EN 60332-1