MEDIUM VOLTAGE
6/10 kV - 18/30 kV |
IEC 60502-2 Reference Norm
|
X-VOLT RHZ1 (S) Cu / OL / 2OL
Conductor:
Annealed electrolytic copper conductor, class 2.
Optionally, with longitudinal sealing (cable type -2OL).
Internal semiconductor:
Screen above the conductor, made of thermosetting semiconductor material.
Insulation:
Cross-linked polyethylene (XLPE), cross-linked in dry nitrogen atmosphere.
External semiconductor:
Screen above the insulation, made of thermosetting and strippable semiconductor material.
Copper screen:
Screen of Cu wires and cross-wound of Cu tape, with a minimum cross-section of 16 mm2
Longitudinal sealing:
Hygroscopic tape completely (cable type –OL and -2OL).
External sheath:
External sheath of fire-retardant and halogen-free polyolefin, red colour with two grey bands. (for S type)
Applications:
Cable for fixed installations. Suitable for the transmission and
distribution of electricity in a medium voltage network. Can be used indoors, outdoors and in underground applications.
Halogen-free cable with low emission of smoke and non-propagator of flame. Safety cable (S).
CHARACTERISTICS
Design standards:
IEC 60502-2
Nominal voltages:
6/10 kV, 8.7/15 kV, 12/20 kV and 18/30 kV
Maximum temperature of the conductor:
90ºC
Maximum temperature in short circuit:
250ºC (maximum 5 s)
Bending radius:
15 x Ø ext.
Halogen-free:
as per UNE-EN 50267
Low emission of smoke:
as per UNE-EN 61034
Non-propagator of flame:
as per UNE-EN 60332-1
|