MEDIUM VOLTAGE
12/20 kV 18/30 kV |
|
X-VOLT HEPRZ1 AL
Conductor:
Electrolytic aluminium conductor, class 2.
Optionally, with longitudinal sealing (cable type -2OL)
Internal semiconductor:
Screen above the conductor, made of thermosetting semiconductor material
Insulation:
High module ethylene propylene rubber (HEPR), cross-linked in dry nitrogen atmosphere.
External semiconductor:
Screen above the insulation, made of thermosetting and strippable semiconductor material.
Copper screen:
Screen of Cu wires and cross-wound of Cu tape, with a minimum cross-section of 16 mm2
Separator:
Polyester tape completely covering the screen to facilitate the
stripping of the outer sheath. Optionally, substituted by hygroscopic
strap (cables with longitudinal sealing, type -OL and -2OL)
External sheath:
External sheath of halogen-free polyolefin, red colour.
Applications:
Cable for fixed installations. Suitable for the transmission and
distribution of electricity in a medium voltage network, halogen-free. Can be used indoors, outdoors and in underground applications.
CHARACTERISTICS
Design standards:
UNE-HD 620-9-E (type 9E-1)
Nominal voltages:
12/20 kV and 18/30 kV
Maximum temperature of the conductor:
105ºC
Maximum temperature in short circuit:
250ºC (maximum 5 s)
Bending radius:
15 x Ø ext.
Halogen-free:
as per UNE-EN 50267
|