Cable > TOXFREE® LSZH FR-N1X1G1 Flex

TOXFREE® LSZH
FR-N1X1G1 Flex

Flexible LSZH power cable for public places (ERP and IGH).
ACCORDING TO: IEC 60502-1. BASED ON: NF C 32-323

TOXFREE® FR-N1X1G1 Flex is a LSZH cable, highly recommended for use in public places (ERP and IGH) according to NFC 15-100.

Enhanced Fire Safety | CPR Cca B2ca LSZH
Enhanced flexibility and ease of Installation
ERP and IGH (buildings open to the public and high-rise buildings)

Typical applications of
TOXFREE® LSZH FR-N1X1G1 Flex

Select...
High-occupancy buildings Industrial facilities Data Centres
TOXFREE® LSZH FR-N1X1G1 flex cables provide superior flexibility and ensure fire-retardant, low-smoke, and halogen-free fire safety (B2ca, Cca) for public places and high rise buildings (ERP & IGH).

UK Building Regulations, European CPR and worldwide electrical national codes increasingly mandate LSZH cables in public spaces and high-occupancy buildings—making FR-N1X1G1 flex not just better performance, but often a regulatory requirement. Provide minimal smoke emission (enabling clearer evacuation routes and safer escape conditions during fires), prevent the release of corrosive or chlorine-based toxic gases, and reduces potential for smoke inhalation injuries.

TOXFREE® LSZH FR-N1X1G1 flex cables provide superior flexibility (class 5) and ensure fire-retardant, low-smoke, and halogen-free fire safety (B2ca, Cca) for reliable power in high-risk industrial facilities and construction sites. XLPE insulation provides superior thermal performance (90°C continuous operation) and excellent electrical properties for demanding industrial loads. The LSZH outer sheath meets stringent UK, European and international fire safety standards (CPR B2ca and Cca).

This combination eliminates the need for separate cable specifications, simplifying procurement and ensuring compliance across UK, European and worldwide installations.

FR-N1X1G1 flex Low Smoke Zero Halogen (B2ca, Cca CPR rated) cables are almost compulsory in Data Centres due to their zero downtime tolerance during a possible fire, ensuring safety of people and equipment, in compliance with European and French standards.

The LSZH outer sheath prevents corrosive halogen emissions that could damage sensitive servers, networking equipment, and storage systems worth millions. Minimal smoke production during fire incidents maintains visibility for emergency response and protects delicate electronic components. Class 5 flexibility facilitates installation through raised floors, cable trays, and tight server rack configurations. XLPE insulation ensures reliable 90°C operation under sustained high loads typical of data centre power distribution.

High-occupancy buildings
TOXFREE® LSZH FR-N1X1G1 flex cables provide superior flexibility and ensure fire-retardant, low-smoke, and halogen-free fire safety (B2ca, Cca) for public places and high rise buildings (ERP & IGH).

UK Building Regulations, European CPR and worldwide electrical national codes increasingly mandate LSZH cables in public spaces and high-occupancy buildings—making FR-N1X1G1 flex not just better performance, but often a regulatory requirement. Provide minimal smoke emission (enabling clearer evacuation routes and safer escape conditions during fires), prevent the release of corrosive or chlorine-based toxic gases, and reduces potential for smoke inhalation injuries.

Industrial facilities
TOXFREE® LSZH FR-N1X1G1 flex cables provide superior flexibility (class 5) and ensure fire-retardant, low-smoke, and halogen-free fire safety (B2ca, Cca) for reliable power in high-risk industrial facilities and construction sites. XLPE insulation provides superior thermal performance (90°C continuous operation) and excellent electrical properties for demanding industrial loads. The LSZH outer sheath meets stringent UK, European and international fire safety standards (CPR B2ca and Cca).

This combination eliminates the need for separate cable specifications, simplifying procurement and ensuring compliance across UK, European and worldwide installations.

Data Centres
FR-N1X1G1 flex Low Smoke Zero Halogen (B2ca, Cca CPR rated) cables are almost compulsory in Data Centres due to their zero downtime tolerance during a possible fire, ensuring safety of people and equipment, in compliance with European and French standards.

The LSZH outer sheath prevents corrosive halogen emissions that could damage sensitive servers, networking equipment, and storage systems worth millions. Minimal smoke production during fire incidents maintains visibility for emergency response and protects delicate electronic components. Class 5 flexibility facilitates installation through raised floors, cable trays, and tight server rack configurations. XLPE insulation ensures reliable 90°C operation under sustained high loads typical of data centre power distribution.

Resources for engineers

TOXFREE® LSZH FR-N1X1G1 Flex Technical datasheet Download file
TOXFREE® LSZH FR-N1X1G1 Flex

Technical specifications

Application

Toxfree® ZH FR-N1X1G1 Flex is a LSHF cable. In the event of
fire, it does not emit toxic gases, nor does it give off corrosive gases,
avoiding any possible damage to people or electronic equipment.
For these reasons it is highly recommended for use in public places
such as: hospitals, schools, museums, airports, bus terminals,
shopping centers, offices, laboratories, etc.

Construction

Insulation

XLPE.
The standard identification of insulation conductors according to HD 308, is the following:
1 x Natural.
2 x Blue + Brown.
3 G Blue + Brown + Green/Yellow.
3 x Brown+ Black+ Grey.
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section).
4 G Brown + Black + Grey + Green/Yellow.
4 x Brown + Black + Grey + Blue.
5 G Brown + Black + Grey + Blue + Green/yellow.

Outer sheath

Polyolefin LSZH.
Green colour.
Other colours available on request.

Standards / Compliance

ACCORDING TO: IEC 60502-1. BASED ON: NF C 32-323

Standards and approvals

  • CE.
  • SEC.
  • KEMA-KEUR.
  • AENOR.
  • UKCA
  • RoHS.

 

Disclaimer
The information displayed on this website is provided for reference purposes only and is not legally binding. Specifications, values, and technical data may be subject to change without notice. To obtain verified and up-to-date technical data for a specific cable, please download Top Cable’s official Technical Specification in PDF format. The PDF document constitutes the sole authoritative source of product data.

 

Characteristics

Electrical performance 0,6/1kV
Thermal performance Maximum conductor temperature: 90ºC. Maximum short-circuittemperature: 250ºC (max. 5 s). Minimum service temperature: -40ºC (fixed and protected installations). Minimum installation and handling temperature: 0ºC.
Fire performance Flame non-propagation according to EN 60332-1 and IEC 60332-1. Fire non-propagation according to UNE-EN 60332-3 / IEC 60332-3 EN 50399. Reaction to fire CPR: B2ca-s1a, d1, a1 or Cca -s1a, d1, a1 according to EN 50575. LSZH (Low Smoke Zero Halogen) according to EN 60754-1 and IEC 60754-1. Low corrosive gases emission according to EN 60754-2 / IEC 60754-2. Low smoke emission according to UNE-EN 61034 and IEC 61034.: Light transmittance > 80%.
Mechanical performance Minimum bending radius: x5 cable diameter. Impact resistance: AG2 Medium severity.
Environmental performance Chemical & Oil resistance: Acceptable. UV resistant according to EN 50618. Water resistance: AD8 Submersion.
Installation conditions Open Air. Buried. In conduit.
Other Meter by meter marking.

Why choose our TOXFREE® LSZH FR-N1X1G1 Flex

  • cable icon

    As cable manufacturers, we ensure cost-effective premium quality and lasting performance.

  • laboratory icon

    Our in-house labs guarantee rigorous cable quality, reliability, and standards compliance.

  • global icon

    Global cable delivery solutions—expert logistics for seamless supply.

  • logistic icon

    Full cable stock, ready for fast delivery- shortest lead times.
    Largest European stockholding.

  • EPD icon

    EPD-certified cables: Sustainable manufacturing for your Scope 3 success.

  • client support icon

    Expert, friendly and professional sales team offering a fast & efficient customer service. Global customers are welcome!

Need expert advice, a custom solution, or an RFQ?

FAQ's TOXFREE® LSZH FR-N1X1G1 Flex

The designation FR-N1X1G1 is a French standard code that identifies a low-voltage electrical cable with improved fire resistance (non-fire-propagating), designed without halogens and with high safety characteristics. This means that the cable does not propagate flame or fire, emits little smoke, and does not release toxic gases if combustion occurs. The cable complies with the French standard NF C 15-100, relating to fire safety.

It also complies with the standard relating to safety in Public Access Buildings and the regulations relating to high-rise buildings.

Yes. FR-N1X1G1 cables comply with the Construction Products Regulation (CPR) and are classified Cca-s1,d1,a1, which means they:
• do not propagate fire,
• produce little smoke,
• emit very little corrosive or toxic gas.

They also meet specific French standards such as NF C 15-100 (related to safety), ERP, IGH, NF C32-070, and NF C32-323 for power distribution cables.

A Low Smoke Zero Halogen (LSZH) cable is designed to low corrosive gases emission in the event of a fire, unlike some standard cables. This reduces risks to people and sensitive equipment in densely populated areas.

The FR-N1X1G1 flex and R2V cables (equivalent to the French standard) are both rated 0.6/1 kV, making them interchangeable for low-voltage power distribution applications. The main differences lie in their construction standards and fire resistance: the R2V uses PVC materials (French standard NF C 32-102), while the FR-N1X1G1 flex uses XLPE/LSZH polyolefin materials compliant with major French and European standards. It complies with safety standards for Public Access Buildings, regulations for high-rise buildings and public spaces, and fire safety regulations (NF C 15-100).

In French projects requiring LSZH performance, particularly in infrastructure or commercial building construction, the FR-N1X1G1 flex is increasingly specified as a complement to or replacement for the R2V.

The cable requirements will come into effect one year after the publication of the decree, i.e., on May 17, 2025. The NF C 15-100 standard sets out the main safety and risk prevention requirements for public access buildings and high-rise buildings.

• Protection against electric shock, overvoltage, and fire hazards.

• Mandatory grounding and appropriate protective devices to limit dangers to people and property.

• Verification and certification of the conformity of installations by accredited bodies such as CONSUEL, Socotec, APAVE, or Bureau Veritas before any power is applied.

The NF C 15-100 standard for public access buildings and high-rise buildings imposes strict requirements on electrical safety, cable quality, fire prevention, and the integration of new technologies, with strong European harmonization and rigorous control of installation conformity.

Yes. Compared to standard cables such as R2V, the FR-N1X1G1 offers:
• improved fire safety (no fire propagation)
• low smoke and toxic gas emissions
• enhanced CPR compliance, making it particularly suitable for high-occupancy or sensitive areas.

• Compliant with public access building regulations, high-rise building regulations, and NF C 15-100 (regulations concerning the safety, reliability, and conformity of electrical installations).

In the event of a fire, it does not release hydrochloric acid gas or dense black smoke.

Compliant with IEC 60332 (flame propagation), IEC 61034 (low smoke emission), and IEC 60754 (halogen free) standards.

Compliant with CPR Euroclass Cca, B2ca or Dca depending on the sheath compound specifications.

The main difference lies in the conductor structure. The FR-N1X1G1 flexible cable uses stranded flexible conductors (Class 5 according to IEC 60228), designed to withstand bends and repeated movement without conductor fatigue. The standard cable uses solid or stranded rigid conductors (Class 1 or 2), designed for fixed installations where the cable remains stationary once laid.

The FR-N1X1G1 flexible cable is easier to install. Its Class 5 stranded construction allows it to be run around bends, pulled through conduits, and integrated into cable management systems with significantly less mechanical force than the rigid version. This results in reduced installation time and a lower risk of insulation damage during pulling.

If your application involves mobile equipment, retractable connections, or frequent access for maintenance, the FR-N1X1G1 flexible cable is the appropriate choice.

The R2V uses PVC insulation and an outer PVC sheath, which produces toxic and dense smoke in the event of a fire.
The FR-N1X1G1 flex uses XLPE insulation and an outer sheath made of LSZH polyolefin, offering superior fire safety. Where the use of LSZH (Low Smoke Zero Halogen) materials is mandatory under applicable building regulations or specifications (increasingly common in European public infrastructure), it is the compliant replacement.

The FR-N1X1G1 cable uses XLPE insulation, which offers a maximum conductor operating temperature of 90°C and a short-circuit temperature of 250°C, exceeding that of PVC. The R2V cable, which uses PVC insulation, is limited to a conductor operating temperature of 70°C and a short-circuit temperature of 160°C.

The FR-N1X1G1 flexible cable is clearly recommended for data center environments. Data centers require LSZH cabling to protect server equipment from corrosive halogen gases in the event of a fire, to comply with increasingly stringent fire safety standards, and to accommodate the dense, flexible cabling configurations typical of raised floors, cable ladders, and PDU connections. PVC-based R2V cable does not meet these requirements. The FR-N1X1G1 flexible cable combines the necessary fire performance with the installation flexibility essential in high-density data infrastructures.

Both cables are halogen free, flame retardant, and designed for fire-sensitive environments, but they come from different national standardization traditions. The N2XH flexible cable complies with the German standard DIN VDE 0276-604 and harmonized IEC standards. The FR-N1X1G1 flexible cable is a French standard cable governed by UTE C 32-070 and NF standards, using XLPE insulation with an LSZH polyolefin sheath and a rated voltage of 0.6/1 kV.

In practical terms, both cables offer equivalent fire safety performance (low smoke emission, halogen-free, flame-resistant), but project specifications in France often require the FR-N1X1G1 flexible cable, while pan-European or German-origin projects refer to the N2XH. Mentioning both designations in your technical documentation will allow you to reach both audiences.

The substantial differences are regulatory and commercial: the flexible cable FR-N1X1G1 is specified in the French NF standards and commonly referenced in French public procurement and infrastructure projects, while the flexible cable N2XH is the corresponding designation harmonized at the German/IEC level.