Cable > TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2

TOXFREE®PLUS 331 LSZH
RZ1-K (AS+) FR2

LSZH and fire resistant power cable, for emergency circuits.
ACCORDING TO: IEC 60502-1., UNE 211025.

TOXFREE® PLUS RZ1-K (AS+) is a fire resistant cable, specially designed to ensure the power supply to emergency circuits in the event of fire.

Fire resistant cable
Maintained Circuit Integrity During Fire
Enhanced Fire Safety | CPR Cca B2ca LSZH

Typical applications of
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2

Select...
Emergency circuits Fire alarm systems Tunnels
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain circuit integrity during fires, ensuring continuous power to emergency lighting, alarms, and evacuation systems.
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain alarm circuit integrity during emergencies, guaranteeing early warning and safe evacuation.
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain emergency systems during tunnel fires, ensuring continuous power to ventilation, lighting and communication systems, enabling safe evacuation and firefighter access.
Emergency circuits
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain circuit integrity during fires, ensuring continuous power to emergency lighting, alarms, and evacuation systems.
Fire alarm systems
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain alarm circuit integrity during emergencies, guaranteeing early warning and safe evacuation.
Tunnels
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) fire-resistant cables maintain emergency systems during tunnel fires, ensuring continuous power to ventilation, lighting and communication systems, enabling safe evacuation and firefighter access.

Resources for engineers

TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2 Technical datasheet Download file
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2 DoP Download file
TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2

Technical specifications

Application

TOXFREE® PLUS RZ1-K (AS+) is a fire resistant cable, specially designed to ensure the power supply to emergency circuits in the event of fire. During a fire you need critical circuits to work for life safety (signaling lights, fume extractors, acustic alarms, water pumps, etc) and a secure plant shutdown. For this reason, its use is highly recommended in public places such as: hospitals, tunnels, offices, production plants, laboratories, hotels, etc.

Construction

Insulation

Mica Tape + XLPE.
The standard identification of insulation conductors according to HD 308, is the following:
1 x Natural.
2 x Blue + Brown.
3 G Blue + Brown + Green/Yellow.
3 x Brown+ Black+ Grey.
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section).
4 G Brown + Black + Grey + Green/Yellow.
4 x Brown + Black + Grey + Blue.
5 G Brown + Black + Grey + Blue + Green/yellow.

Outer sheath

Polyolefin LSZH and fire resistant.
Orange colour.

Standards / Compliance

ACCORDING TO: IEC 60502-1., UNE 211025.

Standards and approvals

  • CE.
  • AENOR.
  • RoHS.

Construction Products Regulation

  • B2ca-s1a, d1, a1.
  • Cca-s1b, d1, a1

 

Disclaimer
The information displayed on this website is provided for reference purposes only and is not legally binding. Specifications, values, and technical data may be subject to change without notice. To obtain verified and up-to-date technical data for a specific cable, please download Top Cable’s official Technical Specification in PDF format. The PDF document constitutes the sole authoritative source of product data.

 

Characteristics

Electrical performance 0,6/1kV
Thermal performance Maximum conductor temperature: 90ºC. Maximum short-circuittemperature: 250ºC (max. 5 s). Minimum service temperature: -40ºC (fixed and protected installations). Minimum installation and handling temperature: 0ºC.
Fire performance Flame non-propagation according to EN 60332-1 / IEC 60332-1. Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN50399. Fire resistant (PH120) minimum 120 minutes at 840 ºC:According to IEC 60331-2 / EN 50200 for cable diameter ≤ 20 mm.According to IEC 60331-1 / EN 50362 for cable diameter > 20 mm. Fire resistant category C (180 minutes at 950ºC), W & Z according toBS 6387.Fire resistant category Rf 1h30 or Rf 1h (according to cross-section)according to NBN S21-300-1. Reaction to fire CPR: B2ca-s1a, d1 ,a1 or Cca-s1b, d1, a1 according to EN50575 (see cross-section). Halogen free according to EN 60754-1 / IEC 60754-1. Low corrosive gases emission according to EN 60754-2 / IEC 60754-2. Low smoke emission according to EN 61034 / IEC 61034:Light transmittance > 60%.
Mechanical performance Minimum bending radius: x5 cable diameter. Impact resistance: AG2 Medium severity. Test impact at -25ª according to H604-5D
Environmental performance Chemical & Oil resistance: Acceptable. UV resistant according to EN 50618. Water resistance: AD5 Jets.
Installation conditions Open Air. Buried. In conduit.
Other Meter by meter marking.

Why choose our TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2

  • cable icon

    As cable manufacturers, we ensure cost-effective premium quality and lasting performance.

  • laboratory icon

    Our in-house labs guarantee rigorous cable quality, reliability, and standards compliance.

  • global icon

    Global cable delivery solutions—expert logistics for seamless supply.

  • logistic icon

    Full cable stock, ready for fast delivery- shortest lead times.
    Largest European stockholding.

  • EPD icon

    EPD-certified cables: Sustainable manufacturing for your Scope 3 success.

  • client support icon

    Expert, friendly and professional sales team offering a fast & efficient customer service. Global customers are welcome!

Need expert advice, a custom solution, or an RFQ?

FAQ's TOXFREE® PLUS 331 LSZH RZ1-K (AS+) FR2

Each cable has a standardised designation. The letters and numbers refer to the cable outer sheath, other cable layers, the conductor flexibility or class, its rated voltage and the final cable composition. In the case of RZ1-K (AS+), the letters stand for:

  • R : Cross-linked polyethylene (XLPE).
  • Z1: Halogen-free thermoplastic polyolefin.
  • -K : Flexible copper (class 5) for fixed installations.
  • (AS+) : High-Security fire-resistant cable.
  • 0,6/1 kV: Rated voltage 1.000 Volt

Here, you can find more information about the designation of electrical cables.

  • Flame non-propagation according to UNE-EN 60332-1 / IEC 60332-1.
  • Fire non-propagation according to UNE-EN 60332-3 / IEC 60332-3 and EN 50399.
  • Fire resistant (PH120) minimum 120 minutes at 840 °C.
  • According to IEC 60331-2 / EN 50200 for cable diameter ≤ 20 mm.
  • According to IEC 60331-1 / EN 50362 for cable diameter > 20 mm.
  • Fire resistance category C (180 minutes at 950°C), W & Z according to BS6387.
  • CPR reaction to fire: B2ca-s1a,d1,a1 or Cca-s1b,d1,a1 according to EN 50575.
  • Halogen-free according to UNE-EN 60754-1 / IEC 60754.
  • Low emission of corrosive gases UNE-EN 60754-2 / IEC 60754-2.
  • Low smoke emission according to UNE-EN 61034 / IEC 61034.
  • Light transmittance > 60%.

For more information on the fire tests to which electrical cables are subjected, see this video from the Top Cable channel on YouTube.

TOXFREE® PLUS RZ1-K (AS+), manufactured by Top Cable, has excellent performance:

  • Maximum electrical performance at maximum and minimum temperatures, to impacts, to chemical attacks.
  • It is a flexible cable that is especially suitable for complex and difficult industrial installations.
  • The UV-resistant outer sheath gives the TOXFREE® PLUS RZ1-K (AS+) cable excellent weather resistance, allowing it to be installed outdoors.

These properties ensure a longer service life for the electrical installation.