TOXFREE® ZH ALARMS Z1OZ1-K (AS)

Cable for alarm systems


The TOXFREE® ZH ALARMS Z1OZ1-K (AS) cable is designed to comply with the regulations of Fire Detection and Alarm systems. It is recommended to be used in public places. It should not be used for direct connection to the power supply network or other low impedance sources.

TOXFREE® ZH ALARMS Z1OZ1-K (AS) cable performance

Electrical performance

Low voltage: 300/500V.

Standard

UNE 211025.

Approvals

RoHS

CE

CPR

Cca -s1a, d1, a1 Thermal performance

Maximum service temperature: 70ºC.

Maximum short-circuit temperature: 160ºC (max. 5 s).

Minimum service temperature: -40ºC (static with protection).

Fire performance

Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1. Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399. Halogen free based on UNE-EN 60754-1 and IEC 60754-1. Smoke density based on EN 61034 / IEC 61034. Light transmittance > 60%. Low smoke emission based on UNE-EN 60754-2 and IEC 60754-2. Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.

Mechanical performance

Minimum bending radius:  x5 cable diameter.

Chemical performance

Chemical & Oil: acceptable.

Applications

· Fire detection.

· Fire alarms.

TOXFREE® ZH ALARMS Z1OZ1-K (AS) cable design

Conductor

Electrolytic copper, class 5 (flexible) based on UNE-EN 60228.

Insulation

Special polyolefin insulation with low smoke emission and halogen-free. Conductor identification: red, black.

Screen

Overlapping aluminium - polyester tape screen with 100% coverage + tinned copper drainage wire.

Outer sheath

Outer sheath of fire-retardant polyolefin, red colour, with low smoke emission and halogen-free in case of fire.

Especificaciones de cable


Otras propiedades


CONSTRUCTION PRODUCT REGULATION

  • Cca s1a, d1, a1

Certificados

  • CE

  • RoHS

Norma de referencia

  • UNE 211025

Tecnología


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible) based on UNE-EN 60228.
  • 2. Insulation
    • Special polyolefin insulation with low smoke emission and halogen-free. Conductor identification: red, black.
  • 3. Screen
    • Overlapping aluminium – polyester tape screen with 100% coverage + tinned copper drainage wire.
  • 4. Outer sheath
    • Outer sheath of fire-retardant polyolefin, red colour, with low smoke emission and halogen-free in case of fire.

Otros cables con propiedades similares


SOPORTE TÉCNICO Y COMERCIAL

Si tiene alguna pregunta, póngase en contacto con nosotros.


    ¡Gracias! Su mensaje ha sido enviado, pronto nos pondremos en contacto con usted.

    Para consultar la ficha técnica del cable, indíquenos sus datos.