This Aluminuim cable POWERHARD RV AL U-1000 AR2V is suitable for all types of underground networks for public power distribution, as well as low voltage connexions in industrial plants, urban networks, buildings, etc. Due to its rigidity, its use is recommended in installations with a simple configuration where a flexible cable is not needed.
POWERHARD RV AL U-1000 AR2V cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
UNE-HD 603-5N / XP C 32-321 / IEC 60502-1
Approvals
NF-USE / AENOR / CE / RoHS
CPR Construction Products Regulation
Eca
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation according to EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR:
Eca, according to EN 50575.
Mechanical performance
Minimum bending radius: x 5 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Good.
UV Resistant: UNE 211605 and XP-C 32-321.
Water performance
Water resistance: AD8 Submersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Distribution network.
POWERHARD RV AL U-1000 AR2V cable design
Conductor
Aluminium, class 2 based on EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene type DIX-3 according to HD 603 (XLPE) according to IEC 60502-1 and compound insulation according to XP C 32-321.
The standard identification of insulated conductors according to HD 308, is the following:
1x Natural
2x Blue + Brown
3x Brown + Black + Grey
3x + 1 Brown + Black + Grey + Blue (reduced cross-section)
4G Brown + Black + Grey + Green/Yellow
4x Brown + Black + Grey + Blue
Outer sheath
Flexible PVC, type DMV-18 according to HD 603, type ST2 according to IEC 60502-1 and compound outer sheath according to XP C 32-321. Black or grey color.