TOXFREE ZH RZ1 (AS) AL

Aluminium halogen free (LSHF) cable for power transmission


TOXFREE ZH RZ1 (AS) AL is an aluminium LSHF cable for fixed installations. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. These cables are especially recommended for installation in public places and in installations where safety is a priority.

TOXFREE ZH RZ1 (AS) AL cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE / RoHS

CPR Construction Products Regulation

B2ca s1a, d1, a1, or B2ca s1b, d1, a1

Thermal performance

Maximum conductor temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Minimum installation and handling temperature: -0ºC.

Fire performance

Flame non-propagation based on EN 60332-1 and IEC 60332-1.

Fire non-propagation based on EN 60332-3 / IEC 60332-3 and EN 50399.

LSHF (Low Smoke Halogen Free) based on  EN 60754-1 and IEC 60754-1.

Low smoke emission based on EN 61034 and IEC 61034: Light transmittance > 80%

Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

Reaction to fire CPR: B2ca s1a, d1, a1, or Cca-s1a, d1, a1 according to EN 50575.

Mechanical performance

Minimum bending radius: x 5 cable diameter.

Impact resistance: AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant according to EN 50618. 

Water performance

Water resistance: AD8 Submersion.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Public places.

TOXFREE ZH RZ1 (AS) AL cable design

Conductor

Aluminium, class 2, based on N 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE) according to IEC 60502-1 and type DIX-3 according to HD 603.

The standard identification of insulated conductors according to HD 308 is the following:
1 x        Natural 2 x        Blue + Brown 3 G        Blue + Brown + Green/Yellow 3 x        Brown + Black + Grey 3 x + 1 x  Brown + Black + Grey + Blue (reduced cross-section) 4 G Brown + Black + Grey + Green/Yellow 4x Brown+Black+Grey+Blue 5 G Brown + Black + Grey + Blue + Green/Yellow 6 or more Black numbered + Green/Yellow
Outer sheath

Low Smoke Halogen Free (LSHF) polyolefin type ST8 according to IEC 60502- 1 and type DMZ-E according to UNE 21123-4. Green color.

DOWNLOAD DoP

  • LOW VOLTAGE 0,6/1kV

  • Maximum service temperature: 90ºC.

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

  • Industrial use and public places.

Cable Specifications


ENVIRONMENTAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

CHEMICAL PERFORMANCE

  • UV Resistant: based on UNE 211605.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission according to IEC 60754-2
  • Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
  • Low smoke halogen free according to IEC 60754-1
  • Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x5 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD8 Submersion.

Other properties


APPROVALS

  • AENOR

  • CE

  • KEMA KEUR
  • RoHS

  • SEC

  • UKCA

APPLICATIONS

  • Industrial use.

  • Public places.

CONSTRUCTION PRODUCT REGULATION

  • B2ca s1a, d1, a1

  • B2ca s1b, d1, a1

BASED ON

  • IEC 60502-1 / UNE 21123-4

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

Technology


  • Conductor
    • Aliuminium, class 2, based on UNE-EN 60228 and IEC 60228.
  • Insulation
    • Cross-linked polyethylene (XLPE).
    • The standard identification of insulated conductors according to HD 308 is the following:

      1 x        Natural
      2 x        Blue + Brown
      3 G        Blue + Brown + Green/Yellow
      3 x        Brown + Black + Grey
      3 x + 1 x  Brown + Black + Grey + Blue (reduced cross-section)
      4 G Brown + Black + Grey + Green/Yellow
      4x Brown+Black+Grey+Blue
      5 G Brown + Black + Grey + Blue + Green/Yellow
      6 or more Black numbered + Green/Yellow

  • Outer sheath
    • Low Smoke Zero Halogen (LSZH) polyolefin type ST8 according to IEC 60502- 1 and type DMZ-E according to UNE 21123-4. Green color.

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.



    Your message has been sent. Thank you

    To consult the technical data sheet of the cable, please provide us with your details.


      Your message has been sent. Thank you