POWERHARD F RVFV-K

Armoured cable with double steel or aluminium tape armour.


POWERHARD F RVFV-K cable is especially suitable for fixed installations that may be subject to mechanical aggression. It is highly recommended for use in installations where the presence of rodents could imply a threat to the cable (such as warehouses, production plants and agricultural facilities). At the same time, its use is recommended for street lighting installations.

POWERHARD F RVFV-K cable performance

Electrical performance

LOW VOLTAGE  0,6/1kV

Standard

IEC 60502-1 / UNE 21123-2

Approvals

CE

BUREAU VERITAS

RoHS

Construction Product Regulation

Eca

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

Reduced emission of halogens. Chlorine <15%.

Mechanical performance

Minimum bending radius: x10 cable diameter.

Impact resistance: AG4 High severity.

Rodent proof

Chemical performance

Chemical & Oil resistance: Good

UV Resistant: UNE 211605.

Water performance

Water resistance: AD7 Immersion.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

POWERHARD F RVFV-K cable design

Conductor

Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE).

The standard identification of insulated conductors is the following:

1 x natural

2 x Blue + Brown

3 G Blue + Brown + Green/yellow

3 x  Brown + Black + Grey

3 x + 1 x  Brown + Black + Grey+ Blue (reduced cross section)

4 G  Brown + Black + Grey + Green/yellow

4 x  Brown + Black + Grey + Blue

5 G Brown + Black + Grey + Blue + Green/yellow

6 G or more conductors:   Black numbered + Green/yellow.

Armour bedding

PVC.

Armour

Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.

Outer sheath

Flexible PVC, black colour.

DOWNLOAD DoP

  • LOW VOLTAGE 0,6/1kV

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Maximum service temperature: 90ºC.

  • UNE-EN 60332-1

  • Industrial use.

  • Eca

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Good.

  • UV Resistant: UNE 211605.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Reduced emission of halogens. Chlorine <15%.

MECHANICAL PERFORMANCE

  • Impact resistance: AG4 High severity.

  • Minimum bending radius: x10 cable diameter.

  • Rodent proof

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD7 Immersion

Other properties


APPLICATIONS

  • Industrial use.

APPROVALS

  • BUREAU VERITAS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 – UNE 21123-2

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

CONSTRUCTION PRODUCT REGULATION

  • Eca

International norm

  • IEC 60332-1

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE).
    • The standard identification of insulated conductors is the following:
    • 1 x natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 3 x Brown + Black + Grey
    • 3 x + 1 x Brown + Black + Grey+ Blue (reduced cross section)
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
    • 6 G or more conductors: Black numbered + Yellow/green.
  • 3. Armour bedding
    • PVC.
  • 4. Armour
    • Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.
  • 5. Outer sheath
    • Flexible PVC, black colour.

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.


[recaptcha]


Your message has been sent. Thank you

To download the cable datasheet, please complete the form below

[recaptcha]


Your message has been sent. Thank you