TOXFREE ZH RZ1FZ1-K (AS)

Halogen free (LSZH) armoured cable with steel or aluminium tape armour.


TOXFREE ZH RZ1FZ1-K AS is an armoured LSZH safety cable. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment. For this reason, its use is highly recommended for public places, in installations with presence of rodents, and installations in general where the cable is subject to risk of mechanical aggression.

TOXFREE ZH RZ1FZ1-K AS cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE

RoHS

CPR Construction Products Regulation

Cca-s1b, d1, a1

Thermal performance

Maximum conductor temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on EN 60332-1 and IEC 60332-1.

Fire non-propagation based on EN 60332-3 and IEC 60332-3.

LSZH (Low Smoke Zero Halogen) based on  EN 60754-1 and IEC 60754-1.

Low smoke emission based on EN 61034 and IEC 61034: Light transmittance > 60%

Low corrosive gases emission based on EN 60754-2 and IEC 60754-2.

Mechanical performance

Minimum bending radius: x10 cable diameter.

Impact resistance: AG4 High severity.

Rodent proof

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant: EN 50618.

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Applications

Industrial use.

TOXFREE ZH RZ1FZ1-K AS cable design

Conductor

Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE).

The standard identification of insulated conductors according to HD 308 is the following:

1 x   Natural

2 x   Blue + Brown

3 G  Blue + Brown + Green/yellow

3 x  Brown+ Black+ Grey

4 G  Brown + Black + Grey + Green/yellow

4 x  Brown + Black + Grey + Blue

5 G  Brown + Black + Grey + Blue + Green/yellow

6 or more Black numbered + Green/yellow

Separation sheath

Low smoke zero halogen (LSZH) polyolefin inner sheath.

Armour

Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.

Outer sheath

Low Smoke Zero Halogen (LSZH) polyolefin type ST8 according to IEC 60502-1 and type DMZ-E according to UNE 21123-4. Green colour, non-toxic and fire retardant.


  • LOW VOLTAGE 0,6/1kV

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Maximum service temperature: 90ºC.

  • EN 60332-1 / EN 60332-3 / EN 50267-1 / EN 50267-2 / EN 61034

  • Industrial use.

Cable Specifications


ENVIRONMENTAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

CHEMICAL PERFORMANCE

  • UV Resistant based on EN 50618.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission according to IEC 60754-2
  • Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
  • Low smoke halogen free according to IEC 60754-1
  • Reaction to fire CPR: Cca-s1b, d2, a1 according to EN 50575.

MECHANICAL PERFORMANCE

  • Impact resistance: AG4 High severity.

  • Minimum bending radius: x10 cable diameter.

  • Rodent proof

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPLICATIONS

  • Industrial use.

APPROVALS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 / UNE 21123-4

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

CONSTRUCTION PRODUCT REGULATION

  • Cca s1a, d1, a1

National norm / European:

  • EN 60332-1 / EN 60332-3 / EN 50267-1 / EN 50267-2 / EN 61034

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

OTHERS

  • Meter by meter marking.

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE).
    • The standard identification of insulated conductors is the following:
    • 1 x Natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 3 x Brown+ Black+ Grey
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
    • 6 or more Black numbered + Green/yellow
  • 3. Armour bedding
    • Low smoke zero halogen (LSZH) polyolefin inner sheath.
  • 4. Armour
    • Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.
  • 5. Outer sheath
    • Low Smoke Zero Halogen (LSZH) polyolefin type ST8 according to IEC 60502-1 and type DMZ-E according to UNE 21123-4. Green color, non-toxic and fire retardant.

Other cables with similar properties