TOPDRIVE VFD (EMC) ROZ1-K (AS) 1,8/3 kV

3kV flexible EMC LSZH screened cable for Variable Frequency Drive motors (VFD cables).


TOPDRIVE VFD (EMC) ROZ1-K (AS) 1,8/3kV cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI).

TOPDRIVE VFD (EMC) ROZ1-K (AS) cable performance

Electrical performance

LOW VOLTAGE 1.8/3 kV

Standard

IEC 60502-1 / IEC 60092-353

Approvals

DNV-GL / ABS / CE / RoHS / BUREAU VERITAS / LLOYD'S REGISTER

CPR Construction Product Regulation 

Cca - s1a, d1, a1

Thermal performance

Maximum conductor temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on EN 60332-1 and IEC 60332-1.

Fire non-propagation based on EN 60332-3, IEC 60332-3 and EN 50399.

LSZH (Low Smoke Zero Halogen) based on EN 60754-1 and IEC 60754-1.

Low smoke emission based on EN 61034 and IEC 61034.: Light transmittance > 80%

Low corrosive gases emission based on EN 60754-2 and IEC 60754-2.

Reaction to fire CPR: Cca - s1a, d1, a1, according to EN 50575.

Mechanical performance

Minimum bending radius: x10 cable diameter.

Impact resistance: AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant according to EN 50618.

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Electric fields resistant.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Variable Frequency Drive (VFD)

Electric fields resistant

TOPDRIVE VFD (EMC) ROZ1-K (AS) cable design

Conductor

Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Grounding Conductor

The ground conductor is divided into three conductors; the equivalent cross-section is approximately 50% of the section of the phase conductor.

Insulation

Cross-linked polyethylene (XLPE) according to IEC 60502-1 and type HF XLPE 90oC according to IEC 60092-351.

The standard identification of insulated conductors is the following:

3x + 3G  grey + brown + black + yellow/green (3 G) (from 6 mm2 onwards)

Screen

Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.

The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.

Outer sheath

Polyolefin type ST8 according to IEC 60502-1 and type SHF1 according to IEC 60092-360, black color.

DOWNLOAD DoP

  • LOW VOLTAGE 1,8/3kV

  • Maximum service temperature: 90ºC.

  • Industrial use / Variable Frequency Drive (VFD) / Electric fields resistant

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Good.

  • UV Resistant based on EN 50618.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 1,8/3kV

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission according to IEC 60754-2
  • Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
  • Low smoke halogen free according to IEC 60754-1
  • Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x10 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPROVALS

  • ABS

  • BUREAU VERITAS

  • CE

  • DNV-GL

  • Lloyd’s Register

  • RoHS

APPLICATIONS

  • Industrial use.

  • Variable Frequency Drive (VFD)

BASED ON

  • IEC 60502-1 / IEC 60092-353

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

CONSTRUCTION PRODUCT REGULATION

  • Cca s1a, d1, a1

OTHERS

  • Electric fields resistant.

  • Meter by meter marking.

National norm / European:

  • EN 60332-1 / EN 60332-3

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Grounding Conductor
    • The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
  • 3. Insulation
    • Cross-linked polyethylene (XLPE)
    • The standard identification of insulated conductors is the following:
    • 3x + 3G grey + brown + black + yellow/green (3 x) (from 6 mm2 onwards)
  • 4. Screen
    • Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
  • 5. Outer sheath
    • Polyolefin type ST8 according to IEC 60502-1 and type SHF1 according to IEC 60092-360, black color.