TOXFREE ZH Z1C4Z1-K (AS)

Halogen free (LSZH) screened power cable.


TOXFREE ZH Z1C4Z1-K AS is a screened LSZH safety cable. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment. For this reason, its use is highly recommended for public places and for all installations where it is necessary avoid to electric interference of nearby circuits.

TOXFREE ZH Z1C4Z1-K AS cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE

RoHS

Construction Product Regulation

Cca -s1a, d1, a1

Thermal performance

Maximum conductor temperature: 70ºC.

Maximum short-circuit temperature: 160ºC (max. 5 s).

Minimum service temperature: -40ºC (static, with protection).

Fire performance

Flame non-propagation based on EN 60332-1 and IEC 60332-1.

Fire non-propagation based on EN 60332-3, IEC 60332-3 and EN 50399.

LSZH (Low Smoke Zero Halogen) based on  EN 60754-1 and IEC 60754-1.

Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 80%

Low corrosive gases emission based on EN 60754-2 and IEC 60754-2.

Reaction to fire CPR: Cca -s1a,d1,a1 according to 50575.

Mechanical performance

Minimum bending radius: x5 cable diameter.

Impact resistance: AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant according to EN 50618.

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Ripcord.

Electric fields resistant

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

TOXFREE ZH Z1C4Z1-K AS cable design

Conductor

Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE)

The standard identification of insulated conductors according to HD 308 is the following:

1 x  natural

2 x Blue + Brown

3 G Blue + Brown + Green/yellow

4 G  Brown + Black + Grey + Green/yellow

4 x  Brown + Black + Grey + Blue

5 G  Brown + Black + Grey + Blue + Green/yellow

6 G or more conductors:   Black numbered + Green/yellow.

Screen

Coverage of 100% composed by aluminium-polyester tape and tinned copper braid.

Outer sheath

Low Smoke Zero Halogen (LSZH) polyolefin. Green color, fire retardant. The ripcord allows you to gently tear the outer sheath allowing you to gently peel it away without damaging the screen.

DOWNLOAD DoP

  • LOW VOLTAGE 0,6/1kV

  • Maximum service temperature: 70ºC.

  • Industrial use.

  • Cca -s1a, d1, a1

Cable Specifications


ENVIRONMENTAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

CHEMICAL PERFORMANCE

  • UV Resistant based on EN 50618.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission according to IEC 60754-2
  • Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
  • Low smoke halogen free according to IEC 60754-1
  • Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x5 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 70ºC.

  • Maximum short-circuit
    temperature: 160ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPLICATIONS

  • Industrial use.

APPROVALS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 / UNE 21123-4

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

CONSTRUCTION PRODUCT REGULATION

  • Cca s1a, d1, a1

OTHERS

  • Electric fields resistant.

  • Meter by meter marking.

  • Ripcord.

National norm / European:

  • EN 60332-1 / EN 60332-3

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE)
    • The standard identification of insulated conductors is the following:
    • 1 x natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
    • 6 G or more conductors: Black numbered + Yellow/green.
  • 3. Screen
    • Coverage of 100% composed by aluminium-polyester tape and tinned copper braid.
  • 4. Outer sheath
    • Low Smoke Zero Halogen (LSZH) polyolefin. Green color, fire retardant. The ripcord allows you to gently tear the outer-sheath allowing you to gently peel it away without damaging the screen.