TOXFREE ZH Z1Z1-K (AS)

Flexible and halogen free (LSHF) power cable for public places.


Toxfree® ZH Z1Z1-K (AS) is a LSHF safety cable. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.

TOXFREE® ZH Z1Z1-K (AS) cable performance

Electrical performance

LOW VOLTAGE 0,6/1 kV 

Standard

IEC 60502-1 / UNE 21123-4

Approvals

CE / RoHS

CPR Construction Products Regulation

B2ca -s1a, d1, a1

Thermal performance

Maximum service temperature: 70°C.

Maximum short-circuit temperature: 160ºC (máximo 5 s).

Minimum service temperature: -40ºC (static, with protection).

Fire performance

Flame non-propagation according to EN 60332-1 / IEC 60332-1.

Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN 50399.

LSHF (Low Smoke Halogen Free) according to EN 60754-1 / IEC 60754-1

Low smoke emission according to EN 61034 / IEC 61034: Light transmittance > 80%.

Low corrosive gases emission according to EN 60754-2 / IEC 60754-2.

Reaction to fire CPR, B2ca -s1a, d1, a1 according to EN 50575.

Mechanical performance

Minimum bending radius: 5x cable diameter.

Impact resistance: AG2 Medium severity.

Environmental performance

Chemical & Oil resistance: Acceptable.

UV Resistant: UNE 211605 and EN 50618. Water resistance: AD5 Jets.

Installation conditions

Open Air. Buried. In conduit.

Aplications

Industrial use. Public places.

TOXFREE® ZH Z1Z1-K (AS) cable design

Conductor

Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228.

Insulation

Special low smoke and halogen free polyolefin insulation. The standard identification of insulated conductors according to HD 308 is the following:

6G or more Black numbered + Green/Yellow.

Outer sheath

Low Smoke Halogen Free (LSHF) polyolefin outer sheath, not toxic and fire retardant. Green colour. Other outer sheath colours available on request.

DOWNLOAD DoP

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Maximum service temperature: 70ºC.

  • Public places.

  • B2ca s1a, d1, a1

  • CE

  • IEC 60502-1 / UNE 21123-4

  • Impact resistance: AG2 Medium severity.

Cable Specifications


ENVIRONMENTAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

  • UV Resistant according to EN 50618.

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Halogen free based on EN 60754-1
  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x5 cable diameter.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

THERMAL PERFORMANCE

  • Maximum service temperature: 70ºC.

  • Maximum short-circuit
    temperature: 160ºC (max. 5 s).

  • Minimum service temperature: -40ºC.

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


CONSTRUCTION PRODUCT REGULATION

  • B2ca s1a, d1, a1

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

APPROVALS

  • CE

  • RoHS

BASED ON

  • IEC 60502-1 / UNE 21123-4

APPLICATIONS

  • Industrial use.

  • Public places.

Technology


  • 1. Conductor
    • Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228.
  • 2. Insulation
    • Special low smoke and halogen free polyolefin insulation. The standard identification of insulated conductors according to HD 308 is the following:
    • 6G or more Black numbered + Green/Yellow
  • 3. Outer sheath
    • Low Smoke Halogen Free (LSHF) polyolefin outer sheath, not toxic and fire retardant. Green colour. Other outer sheath colours available on request.

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.



    Your message has been sent. Thank you

    To consult the technical data sheet of the cable, please provide us with your details.


      Your message has been sent. Thank you