TOXFREE ZH ES05Z1-K and H07Z1-K (AS) is a LSHF safety cable. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.
TOXFREE ZH ES05Z1-K and H07Z1-K (AS) cable performance
Electrical performance
LOW VOLTAGE 300/500 V · 450/750 V
Standard
UNE-EN 50525-3-31 / UNE 211002
Approvals
AENOR / HAR / BUREAU VERITAS / CE / RoHS
CPR Construction Products Regulation
B2ca s1a, d1, a1
Thermal performance
Maximum service temperature: 70ºC (EN 50525-3-31).
Maximum short-circuit temperature: 160ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.
LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: B2
ca s1a, d1, a1 , according to EN 50575.
Mechanical performance
Minimum bending radius: x5 cable diameter.
Chemical performance
Chemical & Oil resistance: Acceptable.
Water performance
Water resistance: AD3 Sprays.
Other
Meter by meter marking. (from 10mm2 onwards)
Installation conditions
In conduit.
Applications
Domestic use.
Electrical panel wiring.
Public places.
Packaging
Small cross sections (from 0,75 mm2 to 6 mm2) are supplied in high-resistant boxes. Medium cross sections (from 10 mm2 to 35 mm2) are supplied in 100 m sealed coils. Greater cross sections (>35 mm2) are supplied in drums.
TOXFREE ZH ES05Z1-K and H07Z1-K (A)S cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Extra sliding low smoke halogen free (LSHF) polyolefin insulation.
The standard identification of insulated conductors is the following:
Blue RAL 5015 - Brown RAL 8003 - Black RAL 9005 -Red RAL 3000 - Green/yellow RAL 1021 / RAL 6018 - Grey RAL 7000 - White RAL 9010 - Orange RAL 2003 - Violet RAL 4005
Other colours available on request