TOXFREE ZH N2XH flex

Flexible halogen free (LSHF) power cable for public places.


TOXFREE ZH N2XH flex is a LSHF safety cable for fixed installations. In the event of fire, it does not emit toxic or corrosives gases,preventing any possible harm to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.

TOXFREE ZH N2XH flex cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1

Approvals

KEMA KEUR / CE 

CPR Construction Product Regulation

B2ca s1a, d1, a1

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Minimum installation and handling temperature: 0ºC (on cable surface).

Fire performance

Flame non-propagation according to EN 60332-1 and IEC 60332-1.

Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN 50399.

LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.

Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%

Low corrosive gases emission according to EN 60754-2 and IEC 60754-2.

Reaction to fire CPR: B2ca-s1a, d1, a1 or Cca-s1a, d1, a1 according to EN 50575.

Mechanical performance

Minimum bending radius: x5 cable diameter.

Impact resistance: AG2 Medium severity.

Environmental performance

Chemical & Oil resistance: Acceptable.

UV Resistant: EN 50618.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Public places.

TOXFREE ZH N2XH flex cable design

Conductor

Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE) insulation according to IEC 60502-1.

The standard identification of insulated conductors according to HD 308 is the following:

1 x  Natural

2 x  Blue + Brown

3 G  Blue + Brown + Green/Yellow

3 x  Brown + Black + Grey

3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)

4 G  Brown + Black + Grey + Green/Yellow

4 x  Brown + Black + Grey + Blue

5 G Brown + Black + Grey + Blue + Green/Yellow

Outer sheath

Low Smoke Halogen Free  (LSHF) polyolefin. Black colour.

DOWNLOAD DoP

  • KEMA KEUR / CE & RoHS

  • IEC 60502-1

  • Chemical & Oil resistance: Acceptable

  • Impact resistance: AG2 Medium severity

  • Water resistance: AD5 Jets

Cable Specifications


ENVIRONMENTAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

CHEMICAL PERFORMANCE

  • UV Resistant based on EN 50618.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
  • LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x5 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum installation and handling temperature: 0ºC (on cable surface).
  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPROVALS

  • CE

  • KEMA KEUR

CONSTRUCTION PRODUCT REGULATION

  • B2ca s1a, d1, a1

BASED ON

  • IEC 60502-1

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

International norm

  • IEC 60502-1

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1

Technology


  • 1. Conductor
    • Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE) according to IEC 60502-1.
    • The standard identification of insulated conductors according to HD 308 is the following:
    • 1 x Natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 3 x Brown + Black + Grey
    • 3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
  • 3. Outer sheath
    • Low Smoke Halogen Free (LSHF) polyolefin. Black colour.

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.



    Your message has been sent. Thank you

    To consult the technical data sheet of the cable, please provide us with your details.


      Your message has been sent. Thank you