TOXFREE ZH RZ1-K (AS) / YMz1Kf

Flexible halogen free (LSHF) power cable for public places.


TOXFREE ZH RZ1-K AS (AS) YMz1Kf is a LSZH safety cable. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.

TOXFREE ZH RZ1-K (AS) YMz1Kf cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1 / UNE 211025

Approvals

AENOR / KEMA KEUR / CE / RoHS

CPR Construction Product Regulation

B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see cross-section)

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

LSHF (Low Smoke Halogen Free) based on  UNE-EN 60754-1 and IEC 60754-1.

Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%

Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

Reaction to fire CPR: B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see cross-section), according to EN 50575. 

Mechanical performance

Minimum bending radius: x5 cable diameter.

Impact resistance: AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Acceptable.

UV Resistant: UNE 211605 and EN 50618.

Water performance

Water resistance: AD5 Jets.

Other

Meter by meter marking.

Installation conditions

Open Air.

Buried.

In conduit.

Applications

Industrial use.

Public places.

Packaging

Available in rolls (lengths of  100 m) and drums.

TOXFREE ZH RZ1-K (AS) /YMz1Kf cable design

Conductor

Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

Cross-linked polyethylene (XLPE)

The standard identification of insulated conductors is the following:

1 x  Natural

2 x  Blue + Brown

3 G  Blue + Brown + Green/Yellow

3 x  Brown + Black + Grey

3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)

4 G  Brown + Black + Grey + Green/Yellow

4 x  Brown + Black + Grey + Blue

5 G Brown + Black + Grey + Blue + Green/Yellow

6 G or more conductors:   Black numbered + Green/Yellow

Outer sheath

Low Smoke Halogen Free  (LSHF) polyolefin. Green colour, non-toxic and fire retardant.

DOWNLOAD DoP

  • LOW VOLTAGE 0,6/1kV

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Maximum service temperature: 90ºC.

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

  • Industrial use / Public places.

  • IEC 60502-1 / UNE 211025

  • UV resistant EN 50618

  • B2ca s1a, d1, a1 |||| Cca s1a, d1, a1

Cable Specifications


CHEMICAL PERFORMANCE

  • Chemical & Oil resistance: Acceptable.

  • UV Resistant: based on UNE 211605.

ELECTRICAL PERFORMANCE

  • LOW VOLTAGE 0,6/1kV

FIRE PERFORMANCE

  • Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.

  • Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.

  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%

  • LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.

MECHANICAL PERFORMANCE

  • Impact resistance: AG2 Medium severity.

  • Minimum bending radius: x5 cable diameter.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -40ºC (fixed and protected installations)

WATER PERFORMANCE

  • Water resistance: AD5 Jets.

Other properties


APPROVALS

  • AENOR

  • CE

  • KEMA KEUR
  • RoHS

APPLICATIONS

  • Industrial use.

  • Public places.

PACKAGING

  • Available in rolls (lengths of 50 and 100 m) and drums.

CONSTRUCTION PRODUCT REGULATION

  • B2ca s1a, d1, a1

  • Cca s1a, d1, a1

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

International norm

  • IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

OTHERS

  • Meter by meter marking.

National norm / European:

  • UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034

Technology


  • 1. Conductor
    • Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
  • 2. Insulation
    • Cross-linked polyethylene (XLPE)
    • The standard identification of insulated conductors is the following:
    • 1 x Natural
    • 2 x Blue + Brown
    • 3 G Blue + Brown + Yellow/green
    • 3 x Brown + Black + Grey
    • 3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
    • 4 G Brown + Black + Grey + Yellow/green
    • 4 x Brown + Black + Grey + Blue
    • 5 G Brown + Black + Grey + Blue + Yellow/green
    • 6 G or more conductors: Black numbered + Yellow/green.
  • 3. Outer sheath
    • Low Smoke Halogen Free (LSHF) polyolefin. Green colour, non-toxic and fire retardant.