Electrical performance
LOW VOLTAGE 0,6/1 kV
Standard
IEC 60502-1 / UNE 21123-4
Approvals
CE / RoHS
CPR Construction Products Regulation
B2ca -s1a, d1, a1
Thermal performance
Maximum service temperature: 70°C.
Maximum short-circuit temperature: 160ºC (máximo 5 s).
Minimum service temperature: -40ºC (static, with protection).
Fire performance
Flame non-propagation according to EN 60332-1 / IEC 60332-1.
Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN 50399.
LSHF (Low Smoke Halogen Free) according to EN 60754-1 / IEC 60754-1
Low smoke emission according to EN 61034 / IEC 61034: Light transmittance > 80%.
Low corrosive gases emission according to EN 60754-2 / IEC 60754-2.
Reaction to fire CPR, B2ca -s1a, d1, a1 according to EN 50575.Mechanical performance
Minimum bending radius: 5x cable diameter.
Impact resistance: AG2 Medium severity.Environmental performance
Chemical & Oil resistance: Acceptable.
UV Resistant: UNE 211605 and EN 50618. Water resistance: AD5 Jets.Conductor
Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228.
Insulation
Special low smoke and halogen free polyolefin insulation. The standard identification of insulated conductors according to HD 308 is the following:
6G or more Black numbered + Green/Yellow.
Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin outer sheath, not toxic and fire retardant. Green colour. Other outer sheath colours available on request.
ENVIRONMENTAL PERFORMANCE
Chemical & Oil resistance: Acceptable.
FIRE PERFORMANCE
Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
MECHANICAL PERFORMANCE
Impact resistance: AG2 Medium severity.
Minimum bending radius: x5 cable diameter.
ELECTRICAL PERFORMANCE
LOW VOLTAGE 0,6/1kV
THERMAL PERFORMANCE
Maximum service temperature: 70ºC.
Maximum short-circuit
temperature: 160ºC (max. 5 s).
Minimum service temperature: -40ºC.
WATER PERFORMANCE
Water resistance: AD5 Jets.
CONSTRUCTION PRODUCT REGULATION
B2ca s1a, d1, a1
INSTALLATION CONDITIONS
Buried.
In conduit.
Open Air.
APPROVALS
CE
RoHS
BASED ON
IEC 60502-1 / UNE 21123-4
APPLICATIONS
Industrial use.
Public places.
If you have any questions, please contact us. We’ll do our best to help.