POWERHARD F RVFV-K cable is especially suitable for fixed installations that may be subject to mechanical aggression. It is highly recommended for use in installations where the presence of rodents could imply a threat to the cable (such as warehouses, production plants and agricultural facilities). At the same time, its use is recommended for street lighting installations.
POWERHARD F RVFV-K cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60502-1 / UNE 21123-2
Approvals
BUREAU VERITAS / CE / RoHS
CPR Construction Product Regulation
Eca
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum installation and handling temperature: 0ºC.
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR: Eca, according to EN 50575.
Mechanical performance
Minimum bending radius: x10 cable diameter.
Impact resistance: AG4 High severity.
Rodent proof.
Environmental performance
Chemical & Oil resistance: Good
UV Resistant: UNE 211605.
Water resistance: AD7 Immersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
POWERHARD F RVFV-K cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene insulation type DIX-3 according to UNE-HD 603 and type XLPE according to IEC 60502-1. The standard identification according to HD 308 is:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Green/yellow
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Green/yellow
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Green/yellow
6 G or more Black numbered + Green/yellow.
Separaton sheath
PVC typeDMV-18 according to UNE-HD 603 and type ST2 according to IEC 60502-1.
Armour
Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.
Outer sheath
Flexible PVC outer sheath type DMV18 according to UNE-HD 603 and type ST2 according to IEC 60502-1. Black color.