Electrical performance
Standard
Approvals
UL LISTED / TÜV / RETIE / CE / RoHS
CPR Construction Products Regulation
Thermal performance
Maximum service temperature: 120ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC.
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: Cca -s1b,d2,a1 according to EN 50575.Mechanical performance
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
UV Resistant based on EN 50618 and UL 2556.Water performance
Water presence: AD8 submerged.
Estimated Lifetime
Estimated lifetime 30 years based on UNE-EN 60216-2.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
Applications
Solar PV installations.
Packaging
Conductor
Class 5 (flexible) tinned copper, based on EN 60228 and IEC 60228.
Insulation
Low smoke halogen free (LSHF) rubber (XLEVA type according to UL / E16 according to TÜV).
Outer sheath
Low smoke halogen free (LSHF) rubber (XLEVA type according to UL / E16 according to TÜV). Black colour.
CHEMICAL PERFORMANCE
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excelente
UV Resistant based on EN 50618 and UL 2556.
ELECTRICAL PERFORMANCE
LOW VOLTAGE CA: 0,6/1kV · CC: 1,8 kV ·UL2000V Type PV/RHW-2 · UL 600 V USE-2
FIRE PERFORMANCE
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%
LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.
MECHANICAL PERFORMANCE
Impact resistance: AG2 Medium severity.
Minimum bending radius: x5 cable diameter.
THERMAL PERFORMANCE
Maximum service temperature: 120ºC.
Maximum short-circuit
temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC.
WATER PERFORMANCE
Water resistance: AD8 Submersion.
APPLICATIONS
Solar PV installations.
APPROVALS
CE
RoHS
TÜV
UL LISTED
PACKAGING
Available in rolls (lengths of 50 and 100 m) and drums.
BASED ON
UL PV WIRE / UL USE-2 / EN 50618 / TÜV 2Pfg 1169-08 / UTE C 32-502
INSTALLATION CONDITIONS
Buried.
Open Air.
CONSTRUCTION PRODUCT REGULATION
Cca s1b, d2, a1
OTHERS
Estimated lifetime 30 years based on UNE-EN 60216-2.
Meter by meter marking.
International norm
IEC 60332-1 / IEC 60754-1 / IEC 60754-2 / IEC 61034
National norm / European:
UNE-EN 60332-1 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034 / NFC 32-070 (C2)
If you have any questions, please contact us. We’ll do our best to help.