Electrical performance
LOW VOLTAGE 300/500 V
Standard
UNE 211025
Approvals
RoHS / AENOR
CPR Construction Product Regulation
Cca s1a, d1, a1
Thermal performance
Maximum service temperature: 70ºC.
Maximum short-circuit temperature: 160ºC (max. 5 s).
Minimum service temperature: -15ºC (static with protection).
Fire performance
Flame non-propagation according to EN 60332-1 and IEC 60332-1.
Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN 50399.
LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.
Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%
Low corrosive gases emission according to EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: Cca-s1a, d1, a1 according to EN 50575.Mechanical performance
Minimum bending radius: 10x cable diameter.
Environmental performance
Chemical & Oil resistance: Acceptable.
Water resistance: AD3 SpraysInstallation conditions
Open air. In conduit. On tray.Other
Meter by meter marking.
Applications
Fire detection.
Fire alarms.
Conductor
Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228.
Insulation
Special polyolefin insulation with low smoke emission and halogenfree.
Conductor identification: Red - Black.
Screen
Overlapping aluminium-polyester tape screen with 100% coverage + tinned copper drain wire.Outer sheath
Fire-retardant polyolefin outer sheath with low smoke emission and halogen-free fumes in case of fire. Red colour.
ENVIRONMENTAL PERFORMANCE
Chemical & Oil resistance: Acceptable.
FIRE PERFORMANCE
Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.
ELECTRICAL PERFORMANCE
LOW VOLTAGE 300/500 V
THERMAL PERFORMANCE
Maximum service temperature: 70ºC.
Maximum short-circuit
temperature: 160ºC (max. 5 s).
Minimum service temperature: -15ºC
MECHANICAL PERFORMANCE
Minimum bending radius: x10 cable diameter.
WATER PERFORMANCE
Water resistance: AD3 Sprays
APPROVALS
AENOR
RoHS
BASED ON
UNE 211025
APPLICATIONS
Fire alarms
Fire detection
INSTALLATION CONDITIONS
In conduit.
On tray
Open Air.
OTHERS
Meter by meter marking.