X-VOLT® CU (-OL/-2OL) RHZ1 (S)

Medium voltage copper cable, XLPE insulation


X-VOLT® RHZ1 (S) is a Medium Voltage copper cable halogen-free fand no flame propagation properties for fixed installations. Suitable for transport and distribution of electric power in medium voltage networks.

X-VOLT® RHZ1 (S) cable performance

Electrical performance

MEDIUM VOLTAGE: 6/10 kV, 8,7/15 kV, 12/20 kV and 18/30 kV

Standard

IEC 60502-2 / UNE-HD 620-10E (type 10E-4) Approvals

AENOR 

CPR Construction Product Regulation

Eca

Thermal performance

Maximum service temperature: 90ºC.

Maximum short-circuit temperature: 250ºC (max. 5 s).

Minimum service temperature: -15ºC.

Fire performance

Flame non-propagation according to EN 60332-1 / IEC 60332-1.

LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.

Low corrosive gases emission according to EN 60754-2 and IEC 60754-2.

Low smoke emission according to EN 61034 / 61034. Light transmittance >60%. Reaction to fire CPR: Eca according to EN 50575.

Mechanical performance

Minimum bending radius: 15x cable diameter.

Abrasion resistant. Tear resistant.

Environmental performance

UV resistant according to UNE 211605.

Installation conditions

Open air. Buried. In conduit.

X-VOLT® RHZ1 cable design

Conductor

Electrolytic annealed copper conductor class 2 according to EN 60228 and IEC 60228. Optionally, with longitudinal water tightness (cable type -2OL).

Conductor screen

Screen over the conductor, made of thermosetting semiconductor material.

Insulation

Cross-linked polyethylene type XLPE according to IEC 60502-2 and type DIX3 according to HD 620-1, natural colour. Cross linked in catenary line with nitrogen atmosphere through a triple layer extrusion process.

Insulation screen

Screen over the insulation, made of thermosetting and strippable semiconductor material.

Metalic screen

Copper wires and copper tape screen, with a minimum cross-section of 16mm2.

Longitudinal water tightness

Hygroscopic tape completely covering the screen (cable type –OL and -2OL).

Filling

Additional fireproof polyolefin layer, halogen free.

Outer sheath

Polyolefin outer sheath type ST7 according to IEC 60502-2 and type DMZ2 according to HD 620-1. Red colour with two grey stripes. Other colours under request.


  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Eca

  • AENOR

  • IEC 60502-2.

  • Abrasion resistant.

Cable Specifications


MECHANICAL PERFORMANCE

  • Abrasion resistant.

  • Minimum bending radius: x15 cable diameter.

  • Tear resistant.

FIRE PERFORMANCE

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1

  • Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.

  • Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
  • LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.

  • Reaction to fire CPR: Eca, according to EN 50575.

THERMAL PERFORMANCE

  • Maximum service temperature: 90ºC.

  • Maximum short-circuit
    temperature: 250ºC (max. 5 s).

  • Minimum service temperature: -15ºC

ELECTRICAL PERFORMANCE

  • MEDIUM VOLTAGE 6/10 kV, 8,7/15 kV, 12/20 kV and 18/30 kV.

ENVIRONMENTAL PERFORMANCE

  • UV Resistant: UNE 211605.

Other properties


APPROVALS

  • AENOR

INSTALLATION CONDITIONS

  • Buried.

  • In conduit.

  • Open Air.

CONSTRUCTION PRODUCT REGULATION

  • Eca

BASED ON

  • IEC 60502-2.

  • UNE-HD 620-10E (type 10E-4)

Technology


  • 1. Conductor
    • Electrolytic annealed copper, class 2 according to EN 60228 and IEC 60228. Optionally, with longitudinal water tightness (cable type -2OL).
  • 2. Conductor screen
    • Screen over the conductor, made of thermosetting semiconductor material.
  • 3. Insulation
    • Cross-linked polyethylene type XLPE according to IEC 60502-2 and type DIX3 according to HD 620-1, natural colour. Cross linked in catenary line with nitrogen atmosphere through a triple layer extrusion process.
  • 4. Insulation screen
    • Screen over the insulation, made of thermosetting and strippable semiconductor material.
  • 5. Metalic screen
    • Copper wires and copper tape screen, with a minimum cross-section of 16mm2.
  • 6. Longitudinal water tightness
    • Hygroscopic tape completely covering the screen (cable type –OL and -2OL).
  • 7. Filling
    • Additional fireproof polyolefin layer, halogen free.
  • 8. Outer sheath
    • Polyolefin outer sheath type ST7 according to IEC 60502-2 and type DMZ2 according to HD 620-1. Red colour with two grey stripes. Other colours under request.

 

Other cables with similar properties


TECHNICAL & SALES SUPPORT

If you have any questions, please contact us. We’ll do our best to help.



    Your message has been sent. Thank you

    To consult the technical data sheet of the cable, please provide us with your details.


      Your message has been sent. Thank you