X-VOLT® RHZ1 is a Medium Voltage copper cable halogen-free for fixed installations. Suitable for transport and distribution of electric power in medium voltage networks.
X-VOLT® RHZ1 is a Medium Voltage copper cable halogen-free for fixed installations. Suitable for transport and distribution of electric power in medium voltage networks.
Electrical performance
MEDIUM VOLTAGE: 6/10 kV, 8,7/15 kV, 12/20 kV and 18/30 kV
Standard
IEC 60502-2 ApprovalsAENOR
CPR Construction Product Regulation
Fca
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -15ºC.
LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.
Low corrosive gases emission according to EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: Fca according to EN 50575.Mechanical performance
Minimum bending radius: 15x cable diameter.
Abrasion resistant. Tear resistant.Environmental performance
UV resistant according to UNE 211605.
Installation conditions
Open air. Buried. In conduit.Conductor
Electrolytic annealed copper, class 2 according to EN 60228 and IEC 60228. Optionally, with longitudinal water tightness (cable type -2OL).
Conductor screen
Screen over the conductor, made of thermosetting semiconductor material.
Insulation
Cross-linked polyethylene type XLPE according to IEC 60502-2, natural colour. Cross linked in catenary line with nitrogen atmosphere through a triple layer extrusion process.
Insulation screen
Screen over the insulation, made of thermosetting and strippable semiconductor material.Metalic screen
Copper wires and copper tape screen, with a minimum cross-section of 16mm2.Longitudinal water tightness
Hygroscopic tape completely covering the screen (cable type –OL and -2OL).Filling
Additional fireproof polyolefin layer, halogen free.Outer sheath
Polyolefin outer sheath type ST7 according to IEC 60502-2. Red colour.
MECHANICAL PERFORMANCE
Abrasion resistant.
Minimum bending radius: x 15 cable diameter.
Tear resistant.
FIRE PERFORMANCE
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
THERMAL PERFORMANCE
Maximum service temperature: 90ºC.
Maximum short-circuit
temperature: 250ºC (max. 5 s).
Minimum service temperature: -15ºC
ELECTRICAL PERFORMANCE
MEDIUM VOLTAGE 3,6/6 kV – 6/10 kV.
8,7/15 kV.- 12/20 kV – 18/30 kV
ENVIRONMENTAL PERFORMANCE
APPROVALS
AENOR
INSTALLATION CONDITIONS
Buried.
In conduit.
Open Air.
CONSTRUCTION PRODUCT REGULATION
Fca
BASED ON
IEC 60502-2.