X-VOLT® TSLF AL is a cable for fixed installations. Suitable for transport and distribution of electric power in medium voltage networks. Halogen free. This cable is suitable for indoor, outdoor and buried installations.
X-VOLT® TSLF AL is a cable for fixed installations. Suitable for transport and distribution of electric power in medium voltage networks. Halogen free. This cable is suitable for indoor, outdoor and buried installations.
Electrical performance
MEDIUM VOLTAGE: 24/36 kV.
Standard
HD 620-10K.
Construction Product Regulation
Eca
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -15ºC
Fire performance
Halogen free: according to EN 60754-1 / IEC 60754-1.Reaction to fire CPR: Eca according to EN 50575.
Mechanical performance
Minimum bending radius: x15 cable diameter.
Abrasion-resistant.
Tear-resistant.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Fixed installations.
Other
Meter by meter marking.
Conductor
Aluminium conductor, class 2 according to IEC 60228. Hygroscopic tapes applied in order to achieve longitudinal watertightness on the conductor.
Conductor screen
Cross-linked semiconductor screen applied over conductor in a triple - extrusion process.
Insulation
Cross-linked polyethylene insulation, type DIX8 according to HD 620-1; natural colour. Cross-linked in catenary line with nitrogen atmosphere.
Insulation screen
Cross-linked semiconductor screen applied over insulation in a triple - extrusion process. Bonded to the insulation layer.
Longitudinal sealing
Hygroscopic tape completely covering the screen.
Metallic screen
Metallic screen with copper wires, applied over the semi - conducting tape. The metallic screen shall have a cross section of 25mm2 for 95mm2 core, 35mm2 for 150, 240 for 400mm2 core and 50mm2 for 630mm2 core.
Radial water-blocking barrier
Made up of an aluminium foil/polymer laminate (7) boned to the outer sheath.
External sheath
Polyethylene outer sheath, type DMP 17 according to HD 620-1; black color (with conductive covering).
MECHANICAL PERFORMANCE
Abrasion resistant.
Minimum bending radius: x 15 cable diameter.
Tear resistant.
ELECTRICAL PERFORMANCE
Medium voltage 24/36 kV.
THERMAL PERFORMANCE
Maximum service temperature: 90ºC.
Maximum short-circuit
temperature: 250ºC (max. 5 s).
Minimum service temperature: -15ºC
INSTALLATION CONDITIONS
Buried.
In conduit.
Open Air.
CONSTRUCTION PRODUCT REGULATION
Eca
OTHERS
Meter by meter marking.
If you have any questions, please contact us. We’ll do our best to help.