Electrical performance
LOW VOLTAGE 1,5/1,5 (1,8) kV DC according to EN 50618 | 1,8/3 (3,6) kV AC according to IEC 60502-1
Standard
IEC 60502-1
Approvals
RoHS / CE
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Minimum installation and handling temperature: 0°C (on cable surface).
Fire performance
Flame non-propagation according to EN 60332-1 / IEC 60332-1.
Reduced halogen emission. Chlorine < 15%.
Mechanical performance
Minimum bending radius: x10 cable diameter.
Impact resistance: AG4 High severity.Environmental performance
Chemical resistance: Good.
Grease & mineral oils resistance: Good.
UV Resistant according to EN 50618 and HD 605/A1.
Other
Meter by meter marking.
Applications
Solar PV installations.
Conductor
Aluminium class 2 according to EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene type XLPE according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308, is the following:
1 x Natural
2 x Blue + Brown
3 x Grey + Brown + Black
4 G Brown + Black + Grey + Green/Yellow
4 x Brown + Black + Grey + Blue
Armour
Aluminium wire armour (AWA) is used in single-core cables to avoid parasite currents that may overheat the cable. Galvanized steel wire armour (SWA) is used in multicores cables.
Outer sheath
Special UV resistant PVC, type ST2 according to IEC 60502-1. Black colour.
CHEMICAL PERFORMANCE
Chemical & Oil resistance: Good.
Grease & mineral oils resistance: Good.
UV Resistant based on EN 50618.
FIRE PERFORMANCE
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Reduced halogen emission. Chlorine <15%.
MECHANICAL PERFORMANCE
Impact resistance: AG4 High severity.
Minimum bending radius: x10 cable diameter.
ELECTRICAL PERFORMANCE
LOW VOLTAGE 1,5/1,5kV · ( 1,8) kV DC
THERMAL PERFORMANCE
Maximum service temperature: 90ºC.
Maximum short-circuit
temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
CE
RoHS
BASED ON
IEC 60502-1
APPLICATIONS
Solar PV installations.
If you have any questions, please contact us. We’ll do our best to help.